Electronic Stroke Control
The Neptune Electric Stroke Control allows the capacity of any Neptune Series 500, Series
600 or Series 6000 "dia-PUMP" to be automatically controlled in response to a standard 4-20 mADC process signal. Alternate inputs are 0-5 VDC / 0-10 VDC signal or incremental contact closures. One-piece controller-positioner mounts directly to the pump. No machining or any special drillings or tappings needed to retrofit pump. It is ideal for water/wastewater, power and process industry applications – anywhere that pump flow must be automatically proportioned or varied.
Features:
– Zero and span settings unlimited
– Adjustable dead band
– Adjustable upper and lower limits
Specifications:
- NEMA 4 (IP65) or Explosion-Proof (Class I, Division 1, Groups C & D; dust & ignition-proof rated Class II, Division 1, Groups E, F & G)
- Power supply: single phase 120/240 VAC (switch selectable), 50/60 Hertz, 18 VA load
- Operating temperature: 0°F to 150°F
- Input signal: 4-20 mADC or 0-5 VDC or 0-10 VDC switch selectable. Also accepts incremental contact closures (dry contacts).
- Output: isolated 4-20 mADC; loop-powered, up to 800 OHM load at 24V
- Precise pump stroke positioning accurate to ±0.75%
- Solid state limit switch outputs with LED status indication (for alarms or process control)
- Limit switch rating: open collector 40 mA max. @ 40 VDC